Mitsubishi Electric MELSEC iQ-R Series User Manual page 625

Process cpu module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error
Error name
code
4C05H
Data logging function error
4C06H
Data logging function error
4C07H
Data logging function error
4C0BH
Data logging function error
4C10H
CPU module data backup/
restoration function error
4C11H
CPU module data backup/
restoration function error
4C12H
CPU module data backup/
restoration function error
4C13H
CPU module data backup/
restoration function error
4C14H
CPU module data backup/
restoration function error
4C15H
CPU module data backup/
restoration function error
Error details and cause
• The online change function was executed while
the data logging function specifying the step
number as a sampling or trigger condition was
being executed (data logging status: RUN waiting
(no collection), Condition waiting (no collection),
Start waiting (no collection), Pause, Collecting,
Trigger waiting (collecting before trigger),
Collecting after trigger, or Saving the logging
data).
• System error
• A data logging is attempted to start with a data
storage memory that is different from the one for
the data logging already registered.
• A data logging file that is being transferred is
deleted.
• Reading from (an access to) a data logging file is
failed.
• The specified file does not exist. Or, the specified
subdirectory does not exist.
• The maximum allowable capacity is exceeded.
• The maximum allowable number of files is
exceeded.
• The upper limit of the backup folder number is
exceeded.
• The maximum length (255 characters) of the file
path is exceeded.
• An SD memory card is not inserted.
• The SD memory card is disabled by SM606 (SD
memory card forced disable instruction).
• Reading/writing of data from/to an SD memory
card completed with an error.
• Reading/writing of data from/to the CPU built-in
memory completed with an error.
• The CPU module data backup/restoration
function cannot be executed because a file
password is set to the data.
• Data was restored to the CPU module where the
same data with a file password has already been
stored.
• Any of the following functions that cannot be
executed simultaneously with the CPU module
data backup/restoration function is being
executed: the file transfer function (FTP), data
backup/restoration (iQ Sensor Solution function),
IP address change function, firmware update
function (via the engineering tool), memory copy
function, or online module change function.
• The CPU module data backup/restoration
function is executed when the following functions
are being executed.
 Online change
 File transfer function (FTP server)
Action
• Do not execute the online change function while the data
logging function specifying the step number is being
executed (data logging status: RUN waiting (no collection),
Condition waiting (no collection), Start waiting (no collection),
Pause, Collecting, Trigger waiting (collecting before trigger),
Collecting after trigger, or Saving the logging data).
• Stop the data logging function specifying the step number.
• Check the specified data, and write it to the CPU module
again.
• Check and correct the setting for the data logging to be
started.
• Check and correct the number of files to be saved in the file
switching setting.
• Check that the data logging file is not deleted.
• Check that an SD memory card is inserted.
• Check the file name and subdirectory name. Then, execute
the function again.
• Increase the free space of the SD memory card and CPU
module, and execute the function again.
• Delete files in the SD memory card and CPU module, and
execute the function again.
• Delete backup data in the SD memory card and CPU
module, and execute the function again.
• Check and correct the folder structure or folder/file names of
backup target data, and execute the data backup function
again.
• Insert or re-insert an SD memory card, and execute the
function again.
• Enable the SD memory card operation, and execute the
function again.
• Check that an SD memory card is inserted, and execute the
function again.
• Replace an SD memory card, and execute the function
again.
• The backup data may have been corrupted. Execute the data
restoration function using another backup data.
• Back up data in the CPU built-in memory, initialize the
memory, and write the data back to the original memory.
Then, execute the data backup/restoration function.
• The possible cause is a hardware failure of the restoration
target CPU module. Execute the data restoration function to
another CPU module.
• Delete file passwords, and execute the CPU module data
backup/restoration function.
• Execute the function again after a while.
36 ERROR CODES