Fujitsu AJ 126LELDH Series Design & Technical Manual page 34

Hide thumbs Also See for AJ 126LELDH Series:
Table of Contents

Advertisement

¢ Calculation example
 Example 1
Indoor temperature
28°CDB/20°CWB
• Selection of indoor unit
No
Item
A-1 Cooling heat load
Indoor unit models
A-2
(Example: AU)
A-3 (TCin)r
A-4 (TCin)d
Compensation coefficient of
A-5
pipe length
A-6 (TCin)e
A-7 ∑(TCin)r
A-8 ∑(TCin)d
1-3. Capacity calculation method
Design conditions
Outdoor temperature
35°CDB
Outdoor
unit
Pipe length (L) = 75 m
Indoor
Indoor
unit 1
unit 2
Room 1
Room 2
Room
1
2
kW
6.0
6.0
6.0
AUXK
AUXK
AUXK
024
024
024
kW
7.1
7.1
7.1
kW
7.7
7.7
7.7
0.90
kW
6.9
6.9
6.9
kW
26.3
kW
28.5
- (02-6) -
Pipe length
75 m
Indoor
Indoor
unit 3
unit 4
Room 3
Room 4
3
4
5
2.0
1.5
AUXB
AUXB
009
007
Refer to "Indoor units" of
unit and indoor unit lineup"
2.8
2.2
INFORMATION on page 01-1.
Refer to
3.0
2.4
Refer to
2.7
2.2
Height difference
20 m
Outdoor unit higher side
Indoor
unit 5
Room 5
Remark
"Outdoor
Chapter 1. GENERAL
"Cooling capacity table
(Indoor unit)"
on page 02-13.
"Capacity compensation
coefficient"
on page 02-12.
(A-4) × (A-5)
Sum of A-3
Sum of A-4
1. Model selection and capacity calculation
in

Hide quick links:

Advertisement

Table of Contents
loading