Fujitsu AJ 126LELDH Series Design & Technical Manual page 36

Hide thumbs Also See for AJ 126LELDH Series:
Table of Contents

Advertisement

Calculation method of outdoor unit capacity from capacity tables
Equation for outdoor unit capacity calculation: Y = (Y
NOTE: Refer to
"Cooling capacity table (Outdoor unit)"
using values of X
• Calculation example of 8 HP outdoor units: AJ072LELDH
Outdoor
Total rated
temperature
cooling capacity
of indoor unit
(°CDB)
26.8
(120%)
X2
24.6
(110%)
X1
Capacity ratio of indoor units to outdoor unit (%)
Capacity of outdoor units (kW)
Y = (25.9 -25.4)/(120 - 110) × (117.4 - 110) + 25.4 = 25.8 kW
1-3. Capacity calculation method
y
(X1, Y1)
Capacity ratio of indoor units to outdoor unit, X (%)
and X
.
1
2
18°CDB / 14 °CWB
27°CDB / 19 °CWB
TC
IP
-15
15.5
2.65
.
.
.
.
.
.
35
15.5
3.93
.
.
.
46
15.5
5.94
-15
14.2
2.44
.
.
.
.
.
.
35
14.2
3.61
.
.
.
46
14.2
5.22
(X2, Y2)
(X, Y)
- Y
)/(X
- X
2
1
2
on page 02-75 to find values of Y
Indoor temperature
28°CDB / 20 °CWB
TC
IP
TC
26.9
4.52
29.2
4.89
.
.
.
.
.
.
25.4
7.67
25.9
7.73
.
.
.
Y2
18.4
6.67
6.67
24.6
4.15
26.7
4.49
.
.
.
.
.
.
24.6
7.48
25.4
7.67
.
.
.
Y1
18.2
6.72
46.6
6.72
X
= 110
1
Y
= 25.4
1
- (02-8) -
x
) × (X - X
) + Y
1
1
1
1
30°CDB / 22 °CWB
32°CDB / 23 °CWB
IP
TC
IP
TC
31.8
5.15
32.5
.
.
.
.
.
.
27.0
7.86
27.6
.
.
.
19.5
6.67
19.9
30.9
5.17
31.6
.
.
.
.
.
.
26.4
7.79
27.0
.
.
.
19.3
6.72
19.7
X
X = 117.4
Y
Y
1. Model selection and capacity calculation
and Y
2
IP
5.13
.
.
.
.
7.93
.
.
6.67
5.15
.
.
.
.
7.86
.
.
6.72
= 120
2
= 25.9
2