Fujitsu AJ 126LELDH Series Design & Technical Manual page 38

Hide thumbs Also See for AJ 126LELDH Series:
Table of Contents

Advertisement

• Decision of system capacity
No
Item
C-1 System capacity
• Calculation of actual capacity of each indoor unit
Item
Actual capacity of each
indoor unit
Calculation method of outdoor unit capacity from capacity tables
Equation for outdoor unit capacity calculation: Y = (Y
NOTE: Refer to
"Cooling capacity table (Outdoor unit)"
using values of X
• Calculation example of 10 HP outdoor units: AJ090LELDH
Outdoor
Total rated
temperature
cooling capacity
of indoor unit
(°CDB)
30.8
(110%)
X2
28.0
(100%)
X1
Capacity ratio of indoor units to outdoor unit (%)
Capacity of outdoor units (kW)
Y = (29.3 - 28.6)/(110 - 100) × (104.3 - 100) + 28.6 = 28.9 kW
1-3. Capacity calculation method
1
2
kW
8.0
8.0
y
(X1, Y1)
Capacity ratio of indoor units to outdoor unit, X (%)
and X
.
1
2
18°CDB / 14 °CWB
27°CDB / 19 °CWB
TC
IP
-15
17.7
3.88
.
.
.
.
.
.
35
17.7
5.07
.
.
.
46
17.7
6.67
-15
16.1
3.54
.
.
.
.
.
.
35
16.1
4.63
.
.
.
46
16.1
5.92
Value
26.0
Room
3
4
5
8.0
1.0
1.0
(X2, Y2)
(X, Y)
- Y
)/(X
- X
2
1
2
on page 02-75 to find values of Y
Indoor temperature
28°CDB / 20 °CWB
TC
IP
TC
30.8
6.62
33.4
7.17
.
.
.
.
.
.
28.7
8.63
29.3
8.67
.
.
.
Y2
20.0
6.70
6.70
28.0
6.03
30.4
6.53
.
.
.
.
.
.
28.0
8.59
28.6
8.63
.
.
.
Y1
19.7
6.73
46.6
6.73
X
= 100
1
Y
= 28.6
1
- (02-10) -
Remark
Smaller value of (A-8) and (B-6)
Remark
(C-1) × (A-3)/(A-7)
x
) × (X - X
) + Y
1
1
1
1
30°CDB / 22 °CWB
32°CDB / 23 °CWB
IP
TC
IP
TC
35.1
7.17
35.9
.
.
.
.
.
.
30.6
8.74
31.3
.
.
.
21.4
6.70
21.8
34.0
7.18
34.8
.
.
.
.
.
.
29.9
8.70
30.5
.
.
.
21.1
6.73
21.5
X
X = 104.3
Y
Y
1. Model selection and capacity calculation
and Y
2
IP
7.16
.
.
.
.
8.78
.
.
6.70
7.17
.
.
.
.
8.73
.
.
6.73
= 110
2
= 29.3
2