Mitsubishi Electric melsec q00ujcpu User Manual page 191

Programmable controller
Hide thumbs Also See for melsec q00ujcpu:
Table of Contents

Advertisement

When local devices are set to be monitored and the program "B" is displayed for monitoring, the local device(s)
used in the program "B" can be monitored.
Local devices are set to be
monitored and the
program "B" is monitored.
6 - 40
CPU module
Program execution (A
X0
MOVP K2 DO
X1
MOVP K3 D99
X10
MOVP K4 DO
X11
MOVP K8 D99
X20
MOVP K3 DO
X21
MOVP K6 D99
GX Developer
Figure 6.34 Local device monitor example
B
C)
Program: A
Program: B
Program: C
The local device data of the
program B is displayed.
(Example)
If D0 to D99 are set as a local device,
D0=4 is displayed when X10 is on and
D99=8 is displayed when X11 is on.