(2) Parameter setting
Set the parameters in the PLC system tab of the PLC parameter dialog box.
To perform the service processing, select any of the parameter items in Table6.43.
The setting value of deselected parameter cannot be entered (default: Execute the process as the scan time
proceeds. = 10%).
Item
Execute the process as
Set the percentage of service processing
the scan time proceeds.
for one scan.
Specify service process
Set the time of service processing for one
time.
scan.
Specify service process
Set the number of service processing for
execution counts.
one scan.
Set whether to perform service
Execute it while waiting
processing during waiting time for
for constant scan setting.
constant scan setting.
Figure 6.95 Parameter setting screen
Table6.43 Parameter items
Description
• Range: 1 to 99%
• Unit: 1%
• Range: 0.2ms to 1000ms
• Unit: 0.1ms
• Range: 1 to 10 times
• Unit: 1 time
Setting range
Default when selected =10%
Default when selected =0.2ms
Default when selected
=1 time
Even when the waiting time is
0.2ms or less, the service
-
processing time (0.2ms) will be
added to the scan time at service
processing execution.