(d) Checking executional conditioned device test settings
Select [Online]
[Debug]
device test].
Figure 6.45 Screen for checking executional conditioned device test settings
Remark
1.
For the operating instruction of checking or disabling executional conditioned device test settings, refer to the
following.
GX Developer Version 8 Operating Manual
2.
Usage of the executional conditioned device test can be checked in the special register (SD840).
(e) Cases where executional conditioned device test settings cannot be registered or
disabled
In the following cases, executional conditioned device test setting cannot be registered or disabled.
When multiple settings are to be registered, no setting can be registered if any of the settings applies to the
cases below.
1) Executional conditioned device test settings cannot be registered
• Specified program does not exist.
• Specified step does not exist.
• Specified device does not exist.
• The number of registered executional conditioned device test settings exceeds 32.
2) Executional conditioned device test settings cannot be disabled
• Specified program does not exist.
• Specified step does not exist.
• Specified device does not exist.
• No executional conditioned device test setting has been registered.
[Executional conditioned device test]
CHAPTER6 FUNCTIONS
[Check/disable executional conditioned
1
2
3
4
5
6
7
8
6 - 53