Mitsubishi Electric melsec q00ujcpu User Manual page 405

Programmable controller
Hide thumbs Also See for melsec q00ujcpu:
Table of Contents

Advertisement

(a) Target memory
Select the Standard RAM, Memory card (RAM), or Memory card (ROM) from this list box.
When using the same file name as that of the program, register the file register to the memory specified in the
PLC File tab of the PLC parameter dialog box.
(b) Selecting a file register file
By selecting a memory for the file register, file names of the set file registers are displayed. Select a file register
file.
(c) Setting the size and file name
Set the size of the file register and a file name of the file register file to be written to the CPU module (PLC-side
file name).
1) File register size of the CPU module
The file register size can be set in increments of one point.
Note that each file size is ensured in units of 256 points.
Even if a file register is not specified from ZR0, the created file will have an assignment from ZR0 to the last
number.
For example, if the write range of a file register is specified to be ZR1000 to ZR1791, the created file register
file will have an assignment from ZR0 to ZR1791.
However, because the data in ZR0 to ZR999 are unreliable, specify the file register from ZR0.
The size of the file register is checked in the units of 1K points. Therefore, the file register size must be
specified from R0 in the units of 1K points.
(d) Writing to the CPU module
The file register file of the specified points is registered to the specified memory of the CPU module.
9 - 60

Advertisement

Table of Contents
loading

Table of Contents