Mitsubishi Electric melsec q00ujcpu User Manual page 275

Programmable controller
Hide thumbs Also See for melsec q00ujcpu:
Table of Contents

Advertisement

(4) Accessible devices
Table6.41 shows accessible devices by the serial communication function.
Category
Function input
Function output
Internal
Function register
system device
Special relay
Special register
Input
Output
Internal relay
Latch relay
Annunciator
Edge relay
Link relay
Data register
Link register
Timer
Internal user
device
Retentive
timer
Counter
Link special relay
Link special register
Step relay
Direct input
Direct output
Index register
Index register
*3
File register
File register
Extended data
Extended data register
*3
register
Extended link
Extended link register
*3
register
*1: After changing the number of device points of the CPU module with GX Developer, use the devices within the new device number range.
Decimal and hexadecimal indicate whether a command specified for the MC protocol is decimal or hexadecimal.
*2: From 000005 to 00000F of FX and FY will be indefinite value.
*3: These registers are not supported by the Q00UJCPU.
6 - 124
Table6.41 Accessible devices by the serial communication function
Device
Device code
*2
FX
*2
FY
FD
SM
SD
X
Y
M
L
F
V
B
D
W
Contact
TS
Coil
TC
Current value
TN
Contact
SS
Coil
SC
Current value
SN
Contact
CS
Coil
CC
Current value
CN
SB
SW
S
DX
DY
Z
R
ZR
D
W
Device number range*1
(default value
000000 to 00000F
Hexadecimal
000000 to 00000F
Hexadecimal
000000 to 000004
Decimal
000000 to 002047
Decimal
000000 to 002047
Decimal
000000 to 001FFF
Hexadecimal
000000 to 001FFF
Hexadecimal
000000 to 008191
Decimal
000000 to 008191
Decimal
000000 to 002047
Decimal
000000 to 002047
Decimal
000000 to 001FFF
Hexadecimal
000000 to 012287
Decimal
000000 to 001FFF
Hexadecimal
000000 to 002047
Decimal
000000 to 002047
Decimal
000000 to 001023
Decimal
000000 to 0007FF
Hexadecimal
000000 to 0007FF
Hexadecimal
000000 to 008191
Decimal
000000 to 000FFF
Hexadecimal
000000 to 000FFF
Hexadecimal
000000 to 000019
Decimal
000000 to 032767
Decimal
000000 to 3FD7FF
Hexadecimal
000000 to 093183
Decimal
000000 to 016BFF
Hexadecimal
: Reading/writing are enabled.
Write
Read
: Writing is prohibited.

Advertisement

Table of Contents
loading