1)
NO
Set local devices?
YES
Set the local device range in the Device
tab of the PLC parameter dialog box.
Set a file name for the local devices in the
PLC file tab of the PLC parameter dialog box.
NO
Use the common
pointers?
YES
Set the start pointer number in the PLC
system tab of the PLC parameter dialog box.
Set the names and execution conditions of
programs to be executed in the Program
tab of the PLC parameter dialog box.
Connect the personal computer to which GX
Developer is installed to the CPU module.
Set the RUN/STOP/RESET switch to
STOP and power on the CPU module
(the ERR. LED turns on).
Select [Online]
[Format PLC memory]
in GX Developer and format the program
memory.
Select [Online]
[Write to PLC]
memory/Device memory" for "Target memory"
in GX Developer and write the parameters
and created programs.
Power off the programmable controller
and then on or reset the CPU module.
Set the RUN/STOP/RESET switch to RUN to
change the CPU module in the RUN status.
3)
CHAPTER11 PROCEDURES FOR WRITING PROGRAM TO CPU MODULE
Section 9.14.1
Section 9.14.1
Section 9.10
Section 2.3
*1
Write to PLC screen
*2
"Program
1
2
11
4
5
6
7
8
11 - 8