(g) Performing sampling trace during execution of another sampling trace
The first sampling trace is performed normally. The second sampling trace cannot be performed.
(h) Executing online change
When sampling trace and online change are performed simultaneously, they operate as follows.
1) Performing sampling trace during online change
• The trace point or trigger point is specified by the step number:
The online change is completed normally but the sampling trace is not performed.
• The trace point and trigger point are specified by except the step number:
Both the online change and sampling trace can be performed.
2) Performing online change during execution of sampling trace
• The trace point or trigger point is specified by the step number:
The sampling trace is suspended but the online change is normally performed.
• The trace point and trigger point are specified by except the step number:
Both the online change and sampling trace can be performed.