Check the network compatibility restrictions above 2000 m (6562 ft), see section
site altitude (page
126).

Fuses (IEC)

gG as well as uR or aR fuses for protection against short-circuit in the input power cable or
drive are listed below. Either fuse type can be used for frames R0...R8 if it operates rapidly
enough. The operating time depends on the supply network impedance and the
cross-sectional area and length of the supply cable.
Note 1: See also
(page
Note 2: Fuses with higher current rating than the recommended ones must not be used.
Note 3: Fuses from other manufacturers can be used if they meet the ratings and the melting
curve of the fuse does not exceed the melting curve of the fuse mentioned in the table.

uR and aR fuse

Drive type
Minimum
ACS560
short cir-
cuit cur-
rent
A
3 phases U
= 400 V (380...480 V)
N
02A6-4
48
03A3-4
48
04A0-4
80
05A6-4
80
07A2-4
128
09A4-4
128
12A6-4
200
017A-4
256
025A-4
320
033A-4
TBA
039A-4
TBA
046A-4
TBA
062A-4
380
073A-4
480
088A-4
480
106A-4
700
145A-4
1000
169A-4
1280
206A-4
1520
55).
Input cur-
rent
Rated cur-
rent I
1)
A
A
4.2
25
5.3
25
6.4
32
9.0
32
11.5
40
15.0
40
20.2
50
27.2
63
40.0
80
32.0
63
38.0
63
45.0
80
61.0
100
72.0
125
87.0
160
105
200
145
250
169
315
206
350
uR and aR
2
I
t
Rated
voltage
N
2
A
s
V
125
690
125
690
275
690
275
690
490
690
1000
690
1800
690
3600
690
1450
690
1450
690
2550
690
4650
690
8500
690
16000
690
15000
690
28500
690
46500
690
68500
690
105000
690
Technical data 111
Installation
Bussmann
IEC 60269
designation
size
type
170M2694
00
170M2694
00
170M2695
00
170M2695
00
170M2696
00
170M2696
00
170M2697
00
170M2698
00
170M2699
00
170M1565
000
170M1565
000
170M1566
000
170M1567
1
170M1568
000
170M1569
1
170M3815
1
170M3816
1
170M3817
1
170M3818
1

Hide quick links: