Mechanical installation

All brake resistors must be installed outside the drive. Follow the resistor manufacturer's
instructions.

Electrical installation

Checking the insulation of the assembly
Follow the instructions given in section
Connection diagram
See section
Connection diagram (page
Connection procedure
See section
Connection procedure, frames R0...R2 (page
Connect the thermal switch of the brake resistor as described in section
system against thermal overload (page

Start-up

Note:
Protective oil on the brake resistors will burn off when the brake resistor is used for the first
time. Make sure that the airflow is sufficient.
Set the following parameters:
1. Disable the overvoltage control of the drive with parameter .
2. Set the source of parameter to point to the digital input where the thermal switch of the
brake resistor is wired.
3. Set parameter to .
4. Enable the brake chopper by parameter . If is selected, set also the brake resistor
overload protection parameters and according to the application.
5. Check the resistance value of parameter .