One, two or three Pt100 sensors for motor temperature measurement can be
connected between an analog input and output as shown below. Do not connect both
ends of the cable shields directly to ground, nor connect the capacitor at one end to
86 Electrical installation
the ground and another end directly to ground.
1...3 × Pt100
T
1) Set the appropriate analog input unit to V (volt) in parameter group 12 Standard AI.
2) Select the excitation mode in parameter group 13 Standard AO.
WARNING!
As the inputs pictured above are not insulated according to IEC 60664, the
WARNING! As the inputs pictured above are not insulated according to IEC 60664, the
connection of the motor temperature sensor requires double or reinforced insulation
connection of the motor temperature sensor requires double or reinforced insulation
between motor live parts and the sensor. If the assembly does not fulfill the
between motor live parts and the sensor. If the assembly does not fulfill the requirement, the I/O
requirement, the I/O board terminals must be protected against contact and must
board terminals must be protected against contact and must not be connected to other
not be connected to other equipment or the temperature sensor must be isolated
equipment or the temperature sensor must be isolated from the I/O terminals.
from the I/O terminals.

Safe torque off (X4)

Safe torque off (X4)
For the drive to start, both connections (+24 V DC to IN1 and +24 V DC to IN2) must be
For the drive to start, both connections (+24 V DC to IN1 and +24 V DC to IN2) must
closed. By default, the terminal block has jumpers to close the circuit. Remove the jumpers
be closed. By default, the terminal block has jumpers to close the circuit. Remove the
before connecting an external Safe torque off circuitry to the drive. See chapter
jumpers before connecting an external Safe torque off circuitry to the drive. See
off function (page
147).
chapter
Safe torque off function
Note:
Note: Only 24 V DC can be used for STO. Only PNP input configuration can be used.
Only 24 V DC can be used for STO. Only PNP input configuration can be used.
Control cable connection procedure R0...R8
WARNING!
Obey the instructions in chapter
injury or death, or damage to the equipment can occur.
1. Stop the drive and perform the steps in section
work (page 13)
before you start the work.
2. Remove the front cover(s) if not already removed. See section
frames R0...R2 (page
cable shield (page
52).
Analog signals
T
T
3.3 nF
> 630VAC
on page 167.
Safety instructions (page
68),
Connection procedure, frames R0...R2 (page 68)
AIn
AGND
AOn
AGND
11). If you ignore them,
Precautions before electrical
Connection procedure,
1)
2)
Safe torque
or
Motor