Electrical power network specification
Voltage (U
)
1
Network type
Rated conditional short-circuit
current (IEC 61439-1)
Frequency
Imbalance
Fundamental power factor
(cos phi
)
1
Motor connection data
Motor types
Frequency
Frequency resolution
Current
Switching frequency
Input voltage range 3~ 380...480 V AC. This is indicated in the type designa-
tion label as typical input voltage levels 3~ 400/480 V AC.
Public low voltage networks. TN (grounded), IT (ungrounded) and corner-
grounded TN systems. See section
grounded) and corner-grounded TN systems (page
65 kA when protected by fuses given in the fuse tables
47 to 63 Hz
Max. ± 3% of nominal phase to phase input voltage
0.98 (at nominal load)
Asynchronous AC induction motor
0....500 Hz
0.01 Hz
See section i484355.
2 kHz, 4 kHz, 8 kHz, 12 kHz (depends on the frame and parameter settings)
Technical data 119
Checking the compatibility with IT (un-
63).