Compliance With The En 61800-3:2004 + A1:2012; Definitions; Category C1; Category C2 - ABB ACS560 Hardware Manual

Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

Compliance with the EN 61800-3:2004 + A1:2012

Definitions

EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic
equipment to operate without problems within an electromagnetic environment. Likewise,
the equipment must not disturb or interfere with any other product or system within its locality.
First environment includes establishments connected to a low-voltage network which supplies
buildings used for domestic purposes.
Second environment includes establishments connected to a network not directly supplying
domestic premises.
Drive of category C1: drive of rated voltage less than 1000 V and intended for use in the
first environment.
Drive of category C2: drive of rated voltage less than 1000 V and intended to be installed
and started up only by a professional when used in the first environment.
Note:
A professional is a person or organization having necessary skills in installing and/or starting
up power drive systems, including their EMC aspects.
Drive of category C3: drive of rated voltage less than 1000 V, intended for use in the second
environment and not intended for use in the first environment.

Category C1

The emission limits are complied with the following provisions:
1. The optional EMC filter is selected according to the documentation and installed as
specified in the EMC filter manual.
2. The motor and control cables are selected as specified in this manual.
3. The drive is installed according to the instructions given in this manual.
4. For the maximum motor cable length with 4 kHz switching frequency, see section
Maximum recommended motor cable length (page
WARNING!
In a domestic environment, this product may cause radio inference, in which case
supplementary mitigation measures may be required.

Category C2

The emission limits are complied with the following provisions:
1. (For R0...R2) The optional EMC filter is selected according to the documentation and
installed as specified in the EMC filter manual.
2. The motor and control cables are selected as specified in this manual.
3. The drive is installed according to the instructions given in this manual.
4. For the maximum motor cable length with 4 kHz switching frequency, see section
Maximum recommended motor cable length (page
Technical data 129
120).
120).

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents