Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

3.5 Configuring the COB IDs and process data objects for the receive and transmit message frames.
3.5.2

Activating "free PDO mapping"

Steps
To activate "free PDO mapping" in SINAMICS drive object 2 (Single Motor Module 2), ca
out the following:
1. In the project navigator, open the expert list for the drive as follows: Drive_2 > right-click >
2. Search for parameter p8744 (see screenshot below) to activate free PDO mapping.
Figure 3-27
3. Choose Free PDO mapping (2).
CANopen interface
Commissioning Manual, 12.2004 Edition, 6SL3097-2AA00-0BP1
Expert >
Ex
pert list.
p8744
Free PDO mapping
Free PDO mapping (2)
Commissioning
rry