Control power supply
Connect the cable for the control power to terminal X2 (Fig. 6-25: 11).
Control signals
Connect the cables to the following terminals:
X10, X11 (Fig. 6-25: 10) Main circuit breaker signals and emergency off
signals
X20 – X27 (Fig. 6-25: 7) Control signals of monitored equipment
Fieldbus interface
Connect the cable directly to the fieldbus adapter.
Encoder interface
1. Connect the cable directly to the encoder adapter.
2. Connect the overall shield and the individual shields of the encoder cable to
the copper busbar.
IMPORTANT! DO NOT connect the shields directly to the encoder adapter.
PRODUCT
ACS5000W
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS799208 E01
ELECTRICAL INSTALLATION
REV.
LANG.
PAGE
F
en
112/178