Advertisement

5. Remove the cable insulation at the point of entry (Fig. 6-20: 1).
If the outer cable screen is non-conductive, cut open the cable screen in the
middle of the stripped area (Fig. 6-20: 1). To turn the conductive side inside
out, pull the cable screen ends over the cable insulation (Fig. 6-20: 2). Connect
the screens ends with a continuous conducting foil (Fig. 6-20: 3).
1

Figure 6-20 Preparing control cables for EMC plates

6. Pull the cable through the entry plate.
7. To prevent water from entering the cabinet, fit the grommet tightly and seal
any gaps with silicone.
8. If you had removed the entry plate, remount it and fasten it properly.