5.13. Joining busbars
There are three types of busbars that need to be joined:
–
AC busbars (Fig. 5-10: 1)
–
PE ground busbar (Fig. 5-10: 2)
–
DC busbars (Fig. 5-10: 3)
1
2
3
Figure 5-10 Busbar connections
1. Before installing the joining pieces, grease the bolts to maintain the required
contact pressure.
2. Join the busbars.
3. Tighten the bolts to the torque of 40 Nm.
PRODUCT
ACS5000W
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS799208 E01
MECHANICAL INSTALLATION
REV.
LANG.
PAGE
F
en
81/178