5.6. Aligning transport units
1. Remove the protective covers from the water pipe ends on both sides.
2. Check that a pipe joint has been slid on one pipe end of two adjoining water
pipes.
3. Line up the transport units as shown in "Appendix C - Mechanical drawings".
The units can be lined up either beginning from the left or the right.
4. Align the transport units.
5. Verify the following alignment parameters:
6. Maximum values for the axial misalignment and the angular deflection of two
adjoining water pipes are not exceeded
•
Axial misalignment: ± 3 mm
•
Axial deflection: 5°
PRODUCT
ACS5000W
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS799208 E01
MECHANICAL INSTALLATION
REV.
LANG.
PAGE
F
en
70/178