9.2.5.3. Enabling the local lock

To enable the local lock, set parameter 16.04 to 2 (LOCKED).
With this parameter setting, local control (including the LOC-REM key) is
disabled.
If the CDP control panel or a DriveWindow PC is in local control mode at the
time that the local lock is enabled, they remain in local control mode until they
are switched to remote control mode. This means that the CDP control panel
displays the letter L until you press the
LOC-REM key.
Disabling the local lock
To disable the local lock, set parameter 16.04 to 1 (OPEN).
With this parameter setting, switching between remote and local control is
enabled.

9.2.5.4. Remote control

In remote control mode, operational commands or reference values usually come
from a higher-level control system via fieldbus or
remote I/O.
However, with the following parameter settings it is possible to start and stop the
drive, to set the direction of rotation, and to enter reference values from the CDP
control panel.
11.01 EXT1 START/STOP/DIR = 10 (KEYPAD) or
12.03 EXT REF1 SELECT = 1 (KEYPAD) and
12.02 EXT1/EXT2 SELECT = 1 (EXT1)
11.02 EXT2 START/STOP/DIR 10 (KEYPAD) or
12.06 EXT REF2 SELECT = 1 (KEYPAD) and
12.02 EXT1/EXT2 SELECT = 2 (EXT2)