Electrical Installation; Safety; Overview; Cable Requirements - ABB ACS5000 User Manual

Water-cooled system drives
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

6. Electrical installation

6.1. Safety

DANGER
Improper work can lead to life-threatening injury or DEATH!
The electrical installation must be carried out by qualified personnel
according to the site and equipment requirements, and the relevant
electrical codes.
When the electrical installation is completed, the main and auxiliary
power supply to the drive must not be switched on without the
consent of the ABB commissioning personnel.
Take appropriate measures to prevent the main and auxiliary power
supply from being switched on during installation.

6.2. Overview

The installation includes the following items:
"6.4 Grounding" on page 86
"6.5 Internal wiring" on page 91
"6.6 Cable entries" on page 95
"6.7 Power cables, ground cables, equipotential bonding conductor"
on page 99
"6.8 Auxiliary power cables and control cables" on page 106

6.3. Cable requirements

6.3.1. Power cables

For information on the requirements for power cables, ground cable and
equipotential bonding conductor, see:
ACS5000 power cable specification
Power cables engineering guideline

6.3.2. Auxiliary and control cables

NOTICE
DO NOT lay control cables in parallel to the power supply cables.
If this cannot be avoided, a minimum distance of 30 cm must be
maintained between control and power supply cables.
Cross control and power supply cables at an angle of 90°
For information on the requirements for the auxiliary power cable and the control
cables, see "Auxiliary power and control cables guideline"
PRODUCT
ACS5000W
Hazardous voltage!
Risk of false signals!
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS799208 E01
ELECTRICAL INSTALLATION
REV.
LANG.
PAGE
F
en
85/178

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents