6. Electrical installation
6.1. Safety
DANGER
Improper work can lead to life-threatening injury or DEATH!
–
The electrical installation must be carried out by qualified personnel
according to the site and equipment requirements, and the relevant
electrical codes.
–
When the electrical installation is completed, the main and auxiliary
power supply to the drive must not be switched on without the
consent of the ABB commissioning personnel.
–
Take appropriate measures to prevent the main and auxiliary power
supply from being switched on during installation.
6.2. Overview
The installation includes the following items:
–
"6.4 Grounding" on page 86
–
"6.5 Internal wiring" on page 91
–
"6.6 Cable entries" on page 95
–
"6.7 Power cables, ground cables, equipotential bonding conductor"
on page 99
–
"6.8 Auxiliary power cables and control cables" on page 106
6.3. Cable requirements
6.3.1. Power cables
For information on the requirements for power cables, ground cable and
equipotential bonding conductor, see:
–
ACS5000 power cable specification
–
Power cables engineering guideline
6.3.2. Auxiliary and control cables
NOTICE
–
DO NOT lay control cables in parallel to the power supply cables.
If this cannot be avoided, a minimum distance of 30 cm must be
maintained between control and power supply cables.
–
Cross control and power supply cables at an angle of 90°
For information on the requirements for the auxiliary power cable and the control
cables, see "Auxiliary power and control cables guideline"