10.6.5. Emergency release of a door safety switch
DANGER
Touching energized components can be fatal.
–
Before you unlock a safety switch, de-energize and ground the drive
according to"10.6.2 De-energizing the drive" on page 165.
–
DO NOT unlock the safety switches permanently.
10.6.5.1. Location of safety switches
Each primary and each secondary PCU is equipped with a safety switch. The safety
switches block and release the locking bars, depending on whether or not the drive
is discharged and grounded. This prevents doors from being opened
unintentionally during operation.
In 1700 mm PCUs, the safety switches are on the back of the left door.
In 2100 mm PCUs, the safety switches are on the back of the middle door.
A screw cap on the front of the door marks the exact position.
Figure 10-6 Location of safety switches
1) Safety switch
For the safety switches to work and to be able to open the doors, auxiliary power
supply is required.
PRODUCT
ACS5000W
Hazardous voltages!
1
DOCUMENT KIND
User manual
PREVENTIVE AND CORRECTIVE MAINTENANCE
DOCUMENT ID.
3BHS799208 E01
REV.
LANG.
PAGE
F
en
170/178