8.4. Local operator panel

The operator panel on the control compartment enables the operator to control
the drive without restrictions, provided that all requirements for normal operation
are met. The functions of the local operator panel include:
Connecting and disconnecting the main power supply
Setting the reference value
Starting and stopping the drive system
Displaying: Actual values, status messages and alarm and fault messages
Viewing and setting parameters
Resetting alarm and fault messages
Activating the emergency-off
Testing lights and illuminated push buttons
1
2
3

Figure 8-1 Local operator panel

PRODUCT
ACS5000W
1) CDP control panel
• Starts / stops drive and motor
• Displays status messages
• Displays alarm and fault messages of the drive and
monitored foreign equipment
• Resets alarm and fault messages
For more information, see "9 CDP control panel" on page 133.
2) Main power supply off
• Illuminated push button opens the main circuit breaker
3) Main power supply on
• Illuminated push button charges the DC link and closes the
main circuit breaker
4) Alarm fault lamp
• Flashing light: alarm
• Permanent light: fault
4
5) Emergency-off reset push button
• Resets the emergency-off relay in the drive control system
5
• Flashes when the auxiliary voltage is switched on, or when
an emergency-off switch is pressed
6) Emergency-off latching push button
• Prevents starting when pressed at standstill of the drive
6
• Main circuit breaker opens and DC link discharges when
pressed during operation of the drive