Indoor unit
7. External Static Pressure (E.S.P) & Air Flow
ARNU36GB8A4, ARNU42GB8A4, ARNU48GB8A4
Setting Value
6(59)
60
40.5
65
52.7
70
63.7
75
71.1
80
76.3
85
83.3
91
89.7
95
93.4
100
93.4
105
93.2
Note: 1. The above table shows the correlation between the air rates and E.S.P.
2. The above table shows the available E.S.P. range.
3. If the E.S.P. of the installed indoor is less than the lowest value(as mention in the table), indoor components
can be failed.
Static Pressure(mmAq(Pa))
9(88)
12(118)
15(147)
-
-
-
39.3
-
-
47.1
-
-
56.9
44.7
-
69.7
55.2
-
78.6
67.4
55.9
87.1
78.9
67.6
91.4
86.1
77.0
91.4
88.3
84.9
91.3
88.3
84.9
18(176)
20(196)
22(216)
-
-
-
-
-
-
-
-
-
-
-
-
-
--
-
31.8
-
-
54.2
-
-
66.4
50.6
30.0
75.9
69.5
60.8
81.1
77.4
69.2
Ceiling Concealed Duct (High Sensible)
(Unit: CMM)
23(226)
25(245)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
43.1
-
67.9
51.3
_ 23