2. Specifications
Type
Model
Cooling Capacity
Heating Capacity
Dimensions(WxHxD) Body
Rows x Columns x FPI
Coil
Face Area
Type
Motor Output x Number
Running Current
Fan
Air Flow Rate(H / M / L)
Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Safety Device
Liquid Side
Pipe Connections Gas Side
Drain Pipe(ID)
Net Weight
Noise Level(Sound Press, 1m, H / M / L)
Power Supply
Refrigerant Control
Transmission cable
Color
Notes:
1. Capacities are based on the following conditions:
Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
2. Capacities are Net Capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. Wiring cable size must comply with the applicable local and national codes. And "Electric characteristics"
chapter should be considered for electrical work and design. Especially the power cable and circuit breaker
should be selected in accordance with that.
5. EEV: Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.
Unit
ARNU30GSVA4
kW
8.8
kcal/h
7,500
Btu/h
32,000
kW
9.4
kcal/h
8,100
Btu/h
32,000
mm
1,190 x 346 x 265
inch
46-27/32 × 13-5/8 × 10-7/16
2 x 18 x 19 + 1 x 6 x 19
m
2
0.34
Cross Flow Fan
W
113 x 1
A
0.51
CMM
23.0 / 20.0 / 17.0
CFM
812 / 706 / 600
Direct
BLDC
Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Resin Net(washable)
Fuse
mm(inch)
Ø9.52 (3/8)
mm(inch)
Ø15.88 (5/8)
mm
16 (5/8)
kg(lbs)
16.6 (35.6)
dB(A)
49 / 44 / 42
1, 220 ~ 240, 50
Ø, V, Hz
1, 220, 60
EEV
mm
2
1.0 ~ 1.5 × 2C
White
Wall Mounted
ARNU36GSVA4
10.4
9,000
35,500
10.8
9,300
37,000
1,190 x 346 x 265
46-27/32 × 13-5/8 × 10-7/16
2 x 18 x 19 + 1 x 6 x 19
0.34
Cross Flow Fan
113 x 1
0.81
26.0 / 23.0 / 19.0
918 / 812 / 671
Direct
BLDC
Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Resin Net(washable)
Fuse
Ø9.52 (3/8)
Ø15.88 (5/8)
16 (5/8)
16.6 (35.6)
52 / 47 / 43
1, 220 ~ 240, 50
1, 220, 60
EEV
1.0 ~ 1.5 × 2C
White
Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m
l/s = CMM x 1000/60
Wall Mounted Unit (Standard)