LG MULTI V ARNU07GTUA4 Engineering Product Data Book page 478

Hide thumbs Also See for MULTI V ARNU07GTUA4:
Table of Contents

Advertisement

8. Electric Characteristicss
Model
ARNU07GQAA4
ARNU09GQAA4
ARNU12GQAA4
ARNU15GQAA4
ARNU07GQAA4
ARNU09GQAA4
ARNU12GQAA4
ARNU15GQAA4
Symbols:
MCA : Minimum Circuit Amperes (A)
MFA : Maximum Fuse Amperes(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amperes(A)
IFM : Indoor Fan Motor
Note :
1. Voltage Range
Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the
listed range limits.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MCA/MFA
MCA = 1.25 x FLA
MFA ≤ 4 x FLA
( Next lower standard fuse rating. Minimum 15A)
4. Select wire size based on the larger value on the MCA.
5. Instead of fuse, use Circuit Breaker.
Units
Type
Hz
Volts
Voltage Range
QA
QA
Min.:198,
50
220-240
QA
Max.:264
QA
QA
QA
Min.:198,
60
220
Max.:242
QA
QA
Power Supply
IFM
MCA
MFA
kW
FLA
0.34
15
0.048
0.27
0.34
15
0.048
0.27
0.36
15
0.048
0.29
0.36
15
0.048
0.29
0.34
15
0.048
0.27
0.34
15
0.048
0.27
0.36
15
0.048
0.29
0.36
15
0.048
0.29
Input(W)
Cooling Heating
15
15
15
15
18
18
24
24
15
15
15
15
18
18
24
24
_ 13
Console

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multi v arnu09gtua4Multi v arnu12gtua4Multi v arnu18gtta4Multi v arnu24gtta4Multi v arnu09gtla4Multi v arnu12gtla4 ... Show all

Table of Contents