Indoor unit
10. Installation
Bolt pitch
• Positioning of holes for fastening to the wall
(Unit:mm)
Type
A
CEA, CEU
858
CFA, CFU
1136
1. Use the Installation mount for installation. Check
whether the wall is strong enough to bear the
weight of the unit or not. if there is a risk, reinforce
the wall before installing the unit.
2. The unit requires a minimum 100 mm clearance
below the unit for air intake. Also, ensure the unit is
leveled when installed so that drainage flows
smoothly. If inclined, water can leak.
3. Depending upon the shape and nature of the wall
surface, operating sound may become bigger.
How to open/close front panel
• How to open/close the front panel
(1) Open the lid of control panel(Both left and right)
(2) Remove screws(Both left and right)
(3) Lift the front panel of the unit
• To close, perform the procedure in opposite
order.
A
(1)
(2)
(3)
Floor Standing
(2)
(1)
_ 23