Indoor unit

2. Specifications

Type
Model
Cooling Capacity
Heating Capacity
Casing
Body
Dimensions(WxHxD)
Front Panel
Rows x Columns x FPI
Coil
Face Area
Type
Motor Output x Number
Running Current
Fan
Air Flow Rate(H / M / L)
Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Safety Device
Liquid Side
Pipe Connections Gas Side
Drain Pipe(Internal Dia.)
Net Weight
Body
Packaged
Noise Level(Sound Press, 1.5m, H / M / L)
Power Supply
Refrigerant Control
Transmission cable
Panel Color
Panel Name(Accessory)
Notes:
1. Capacities are based on the following conditions:
Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
2. Capacities are Net Capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. Wiring cable size must comply with the applicable local and national codes. And "Electric characteristics" chapter should be considered for
electrical work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
5. EEV: Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.
7. For the detail information of installation, please refer to the each installation section of standard model part.
2 _
Compact Model
Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h
mm
inch
mm
inch
m
2
W
A
CMM
cfm
Microprocessor, Thermostat for cooling and heating
mm(inch)
mm(inch)
mm(inch)
kg(lbs)
kg(lbs)
dB(A)
Ø, V, Hz
mm
2
* Model Name
E:Basic, F:Plasma
4 Way Ceiling Cassette
ARNU09GTR*4
2.8
2,400
9,600
3.2
2,800
10,900
Galvanized Steel Plate
570 x 214 x 570
22-7/16 x 8-7/16 x 22-7/16
700 x 22 x 700
27-9/16 x 7/8 x 27-9/16
1 x 8 x 18
0.21
Turbo Fan
43 x 1
0.2
8.2 / 7.4 / 6.9
289 / 261 / 244
Direct
BLDC
Foamed polystrene
Fuse
Ø6.35(1/4)
Ø12.7(1/2)
25(1)
12.6(27.8)
15.3(33.7)
33 / 31 / 28
1, 220-240, 50
1, 220, 60
EEV
CVV-SB 1.0~1.5 x 2C
Morning fog
PT-UQC
Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m
l/s = CMM x 1000/60
3