Indoor unit
10. Installation

10.2 Ceiling dimension and hanging bolt location

n Installation of Unit
Install the unit above the ceiling correctly.
CASE 1
POSITION OF SUSPENSION BOLT
• Apply a joint-canvas between the unit and duct to
absorb unnecessary vibration.
• Install the unit leaning to a drainage hole side as
a figure for easy water drainage.
CASE 2
POSITION OF CONSOLE BOLT
• A place where the unit will be leveled and that can sup-
port the weight of the unit.
• A place where the unit can withstand its vibration.
• A place where service can be easily performed.
Dimension
A
B
Capacity(kBtu/h)
5/7/9
733 772 628 700 36 190 20 660 155 700
12/15/18
933 972 628 700 36 190 20 860 155 900
21/24
1133 1172 628 700 36 190 20 1060 155 1100
(Unit:mm)
C
D
E
F
G
H
I
E
D
C
J
Ceiling Concealed Duct(Low Static)
G
J
A
B
H
Drainage hole
M10 Nut
X 4
M10 washer
X 4
M10 washer
X 4
M10 Nut
X 8