Indoor unit
10. Installation

10.1 Selection of the best location

Install the air conditioner in the location that satisfies the
following conditions.
• The place shall easily bear a load exceeding four times
the indoor unit's weight.
• The place shall be able to inspect the unit as given in
the
figure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.(Suitable
dimension "H" is necessary to get a slope to drain as
figure.)
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical
noise.
• The place where air circulation in the room will be good
.
• There should not be any heat source or steam near the
unit.
• The servicing inspection hole in the ceiling should be as
large as the product.
• The selection of the servicing hole should be approved
by the customer.
[L1 / L2 / L3 Chassis]
Capacity (kBtu/h)
5/7/9
12/15/18
21/24
28 _
Ceiling Concealed Duct(Low Static)
(Unit: mm)
A
B
800
800
800
1000
800
1200
Top view
(Unit: mm)
Control box
600
Inspection hole
(600 x 600)
Side view
(unit: mm)
• Suitable dimension "H" is necessary to get a slope
to drain as shown in the figure
B(Min)
A(Min)
Service Space
600
H=20 or more
Ceiling
A
B