Indoor unit
10. Installation
• Please read this instruction sheet completely before installing the product.
• When the power cord is damaged, replacement work shall be performed by authorized personnel only.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
Required Parts
• Connecting cable
• Pipes: Gas side
Liquid side
• Hanging Bolt
(W 3/8 or M10 length 650mm)
• Insulated drain hose
• Additional Drain hose
10.1 Selection of the best location
Install the air conditioner in the location that satisfies the fol-
lowing conditions.
• The place shall easily bear a load exceeding four times the
indoor unit's weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.
(Suitable dimension "H" is necessary to get a slope to drain
as figure.)
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical
noise.
• The place where air circulation in the room will be good .
• There should not be any heat source or steam near the unit.
• The servicing inspection hole in the ceiling should be as
large as the product
• The selection of the servicing hole should be approved by
the customer
Air outlet vents
Air intake vents
Wired LCD Remote Control
Required Tools
• Level
• Screw driver
• Electric drill
• Hole core drill
• Flaring Tool set
• Torque Wrenches
• Hexagonal Wrench
• Gas-leak detector
• Thermometer
Ceiling Concealed Duct (High Sensible)
Air filters
TEMP
Remote Controller
Top view
[600(23-5/8) x 600(23-5/8)]
600
[Unit: mm(inch)]
(23-5/8)
Front view
[Unit: mm(inch)]
600
(23-5/8)
H = 20(25/32) or more
_ 29