LG MULTI V ARNU07GTUA4 Engineering Product Data Book page 359

Hide thumbs Also See for MULTI V ARNU07GTUA4:
Table of Contents

Advertisement

Indoor unit
8. Electric Characteristics
Model
Type
ARNU48GBRZ4
BR
ARNU76GB8Z4
B8
ARNU96GB8Z4
B8
ARNU48GBRZ4
BR
ARNU76GB8Z4
B8
ARNU96GB8Z4
B8
Symbols:
MCA : Min, Circuit Amps(A)
MFA : Max. Fuse Amps(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amps(A)
IFM : Indoor Fan Motor
12 _
Fresh Air Intake Unit
Units
Hz
volts
Voltage Range
Max: 264
50
220-240
Min: 198
Max: 242
60
220
Min: 198
Note :
1. Voltage range
Units are suitable for use on electrical systems where voltage
supplied to unit terminals is not below or above the listed range
limits,
2. Maximum allowable voltage unbalance between phases is 2%
3. MCA/MFA
MCA=1.25 x FLA
MFA≤ 4 x FLA
(Next lower standard fuse rating. Min. 15A)
4. Select wire size based on the MCA
5. Instead of fuse, use Circuit Breaker.
Power Supply
IFM
MCA
MFA
kW
1.5
15
0.20
2.7
15
0.38
3.7
15
0.38
1.5
15
0.20
2.7
15
0.38
3.7
15
0.38
Input(W)
FLA
Cooling Heating
0.78
169
169
1.36
230
230
2.15
360
360
0.78
169
169
1.36
230
230
2.15
360
360

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multi v arnu09gtua4Multi v arnu12gtua4Multi v arnu18gtta4Multi v arnu24gtta4Multi v arnu09gtla4Multi v arnu12gtla4 ... Show all