Indoor unit
6. Capacity Tables
Outdoor
Capacity
air temp.
Index
(DB, °C)
10
12
14
16
18
20
21
23
3.6
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
4.5
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
5.6
25
27
29
31
33
35
37
39
Notes:
TC: Total Capacity(kW)
SHC: Sensible Heat Capacity(kW)
1. Capacity tables show the representative value of conditions
which may occur.
16 _
Ceiling Cassette 4-way
20
23
14
16
TC
SHC
TC
SHC
TC
kW
kW
kW
kW
kW
2.4
2.1
2.9
2.3
3.3
2.4
2.1
2.9
2.3
3.3
2.4
2.1
2.9
2.3
3.3
2.4
2.1
2.9
2.3
3.3
2.4
2.1
2.9
2.3
3.3
2.4
2.1
2.9
2.3
3.3
2.4
2.1
2.9
2.3
3.3
2.4
2.1
2.9
2.3
3.3
2.4
2.1
2.9
2.3
3.3
2.4
2.1
2.9
2.3
3.3
2.4
2.1
2.9
2.3
3.3
2.4
2.1
2.9
2.3
3.3
2.4
2.1
2.9
2.3
3.3
2.4
2.1
2.9
2.3
3.3
2.4
2.1
2.9
2.3
3.3
2.4
2.1
2.9
2.3
3.3
3.0
2.7
3.6
3.0
4.2
3.0
2.7
3.6
3.0
4.2
3.0
2.7
3.6
3.0
4.2
3.0
2.7
3.6
3.0
4.2
3.0
2.7
3.6
3.0
4.2
3.0
2.7
3.6
3.0
4.2
3.0
2.7
3.6
3.0
4.2
3.0
2.7
3.6
3.0
4.2
3.0
2.7
3.6
3.0
4.2
3.0
2.7
3.6
3.0
4.2
3.0
2.7
3.6
3.0
4.2
3.0
2.7
3.6
3.0
4.2
3.0
2.7
3.6
3.0
4.2
3.0
2.7
3.6
3.0
4.2
3.0
2.7
3.6
3.0
4.2
3.0
2.7
3.6
3.0
4.2
3.8
3.2
4.5
3.5
5.2
3.8
3.2
4.5
3.5
5.2
3.8
3.2
4.5
3.5
5.2
3.8
3.2
4.5
3.5
5.2
3.8
3.2
4.5
3.5
5.2
3.8
3.2
4.5
3.5
5.2
3.8
3.2
4.5
3.5
5.2
3.8
3.2
4.5
3.5
5.2
3.8
3.2
4.5
3.5
5.2
3.8
3.2
4.5
3.5
5.2
3.8
3.2
4.5
3.5
5.2
3.8
3.2
4.5
3.5
5.2
3.8
3.2
4.5
3.5
5.2
3.8
3.2
4.5
3.5
5.2
3.8
3.2
4.5
3.5
5.2
3.8
3.2
4.5
3.5
5.2
Indoor air temp. (DB/WB, °C)
26
27
28
18
19
20
SHC
TC
SHC
TC
kW
kW
kW
kW
2.5
3.6
2.5
3.9
2.5
3.6
2.5
3.9
2.5
3.6
2.5
3.9
2.5
3.6
2.5
3.9
2.5
3.6
2.5
3.9
2.5
3.6
2.5
3.9
2.5
3.6
2.5
3.9
2.5
3.6
2.5
3.9
2.5
3.6
2.5
3.9
2.5
3.6
2.5
3.9
2.5
3.6
2.5
3.9
2.5
3.6
2.5
3.9
2.5
3.6
2.5
3.9
2.5
3.6
2.5
3.9
2.5
3.6
2.5
3.8
2.5
3.6
2.5
3.7
3.2
4.5
3.3
4.8
3.2
4.5
3.3
4.8
3.2
4.5
3.3
4.8
3.2
4.5
3.3
4.8
3.2
4.5
3.3
4.8
3.2
4.5
3.3
4.8
3.2
4.5
3.3
4.8
3.2
4.5
3.3
4.8
3.2
4.5
3.3
4.8
3.2
4.5
3.3
4.8
3.2
4.5
3.3
4.8
3.2
4.5
3.3
4.8
3.2
4.5
3.3
4.8
3.2
4.5
3.3
4.8
3.2
4.5
3.3
4.7
3.2
4.5
3.3
4.6
3.8
5.6
3.9
6.0
3.8
5.6
3.9
6.0
3.8
5.6
3.9
6.0
3.8
5.6
3.9
6.0
3.8
5.6
3.9
6.0
3.8
5.6
3.9
6.0
3.8
5.6
3.9
6.0
3.8
5.6
3.9
6.0
3.8
5.6
3.9
6.0
3.8
5.6
3.9
6.0
3.8
5.6
3.9
6.0
3.8
5.6
3.9
6.0
3.8
5.6
3.9
6.0
3.8
5.6
3.9
6.0
3.8
5.6
3.9
5.8
3.8
5.6
3.9
5.7
2. Refer to Capacity Correction Factor in the outdoor unit PDB for
the actual performance data of each indoor unit and outdoor unit
combination.
Cooling capacity
30
32
22
24
SHC
TC
SHC
TC
SHC
kW
kW
kW
kW
2.6
4.3
2.7
4.7
2.6
4.3
2.7
4.7
2.6
4.3
2.7
4.6
2.6
4.3
2.7
4.6
2.6
4.3
2.7
4.5
2.6
4.3
2.7
4.4
2.6
4.3
2.7
4.4
2.6
4.3
2.7
4.3
2.6
4.3
2.6
4.3
2.6
4.2
2.6
4.2
2.6
4.1
2.5
4.2
2.6
4.1
2.5
4.1
2.6
4.0
2.5
4.0
2.6
3.9
2.5
4.0
2.5
3.8
2.4
3.9
2.5
3.8
2.4
3.9
3.4
5.4
3.6
5.9
3.4
5.4
3.6
5.8
3.4
5.4
3.6
5.8
3.4
5.4
3.6
5.7
3.4
5.4
3.6
5.6
3.4
5.4
3.6
5.5
3.4
5.4
3.6
5.5
3.4
5.4
3.6
5.4
3.4
5.3
3.5
5.3
3.4
5.2
3.4
5.3
3.4
5.1
3.4
5.2
3.4
5.1
3.3
5.1
3.4
4.9
3.3
5.0
3.4
4.9
3.2
4.9
3.3
4.8
3.2
4.9
3.2
4.7
3.1
4.8
4.1
6.7
4.2
7.3
4.1
6.7
4.2
7.3
4.1
6.7
4.2
7.2
4.1
6.7
4.2
7.1
4.1
6.7
4.2
6.9
4.1
6.7
4.2
6.9
4.1
6.7
4.2
6.9
4.1
6.7
4.2
6.7
4.1
6.6
4.1
6.6
4.1
6.5
4.1
6.5
4.1
6.4
4.0
6.5
4.1
6.3
3.9
6.4
4.1
6.2
3.9
6.2
4.1
6.1
3.8
6.2
3.9
5.9
3.7
6.1
3.8
5.8
3.7
6.0
kW
2.6
2.6
2.6
2.5
2.5
2.5
2.5
2.5
2.4
2.4
2.4
2.3
2.3
2.3
2.2
2.2
3.5
3.5
3.4
3.4
3.4
3.3
3.3
3.2
3.2
3.2
3.1
3.0
3.0
3.0
2.9
2.8
4.1
4.1
4.1
4.0
4.0
3.9
3.9
3.8
3.7
3.7
3.7
3.6
3.5
3.5
3.4
3.4