Indoor unit
8. Electric Characteristics
Model
ARNU07GSF14
ARNU09GSF14
ARNU12GSF14
ARNU07GSF14
ARNU09GSF14
ARNU12GSF14
Symbols:
MCA: Minimum Circuit Amperes (A)
MFA : Maximum Fuse Amperes(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amperes(A)
IFM : Indoor Fan Motor
Note :
1. Voltage Range
Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the
listed range limits.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MCA/MFA
MCA = 1.25 x FLA
MFA ≤ 4 x FLA
( Next lower standard fuse rating. Minimum 15A)
4. Select wire size based on the MCA.
5. Instead of fuse, use Circuit Breaker.
Units
Type
Hz
Volts
Voltage Range
SF
Max:264
SF
50
220 - 240
Min:198
SF
SF
Max:242
SF
60
220
Min:198
SF
Power Supply
IFM
MCA
MFA
kW
FLA
0.23
15
0.024
0.23
15
0.024
0.23
15
0.024
0.23
15
0.024
0.23
15
0.024
0.23
15
0.024
ARTCOOL (Gallery)
Input(W)
Cooling Heating
0.18
35
35
0.18
35
35
0.18
35
35
0.18
35
35
0.18
35
35
0.18
35
35