Indoor unit

2. Specification

Type
Accessory
Model
Cooling Capacity
Heating Capacity
Casing
Dimensions(WxHxD) Body
Rows x Columns x FPI
Coil
Face Area
Type
Motor Output x Number
Running Current
Air Flow Rate(H / M / L)
(High Mode-factor set)
Fan
External Static Pressure mmAq(Pa)
Air Flow Rate(H / M / L)
(Standard Mode)
External Static Pressure mmAq(Pa)
Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Safety Device
Liquid Side
Pipe Connections Gas Side
Drain Pipe(Internal Dia.)
Net Weight
Noise Level(Sound Press, 1m, H / M / L)
Power Supply
Refrigerant Control
Transmission cable
Notes:
1. Capacities are based on the following conditions:
Cooling
• Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
Heating
• Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. Wiring cable size must comply with the applicable local and national codes. And "Electric characteristics" chapter should be
considered for electrical work and design. Especially the power cable and circuit breaker should be selected in accordance
with that.
5. EEV: Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.
2 _
Ceiling Concealed Duct_Built in (Low Static)
Ceiling Concealed Duct (Built-in (Low Static))
PBSGB30/PBSC30
Unit
ARNU07GB3G4
kW
2.2
kcal/h
1,900
Btu/h
7,500
kW
2.5
kcal/h
2,200
Btu/h
8,500
Galvanized Steel Plate
mm
820 x 190 x 575
inch
32-9/32 x 7-15/32 x 22-5/8
2 x 11 x 21
m
2
0.16
Sirocco Fan
W
19 x 1, 5 x 1
A
0.76
CMM
8.0 / 6.5 / 5.5
cfm
283 / 229 / 194
2(20)
CMM
8.0 / 6.5 / 5.5
cfm
283 / 229 / 194
0(0)
Direct
BLDC
Mi c roprocessor, Thermostat for cool i n g and heati n g Mi c roprocessor, Thermostat for cool i n g and heati n g Mi c roprocessor, Thermostat for cool i n g and heati n g
Foamed polystrene
-
Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor
mm(inch)
Ø6.35(1/4)
mm(inch)
Ø12.7(1/2)
mm(inch)
25.4(1)
kg(lbs)
21(46.3)
dB(A)
33 / 32 / 29
1, 220-240, 50
Ø, V, Hz
1, 220, 60
EEV
mm
2
CVV-SB 1.0~1.5 x 2C
PBSGB30/PBSC30
PBSGB30/PBSC30
ARNU09GB3G4
ARNU12GB3G4
2.8
2,400
9,600
3.2
2,800
10,900
Galvanized Steel Plate
Galvanized Steel Plate
820 x 190 x 575
820 x 190 x 575
32-9/32 x 7-15/32 x 22-5/8
32-9/32 x 7-15/32 x 22-5/8
2 x 11 x 21
0.16
Sirocco Fan
19 x 1, 5 x 1
0.76
9.0 / 7.0 / 6.0
318 / 247 / 212
2(20)
9.0 / 7.0 / 6.0
318 / 247 / 212
0(0)
Direct
BLDC
Foamed polystrene
Foamed polystrene
-
Ø6.35(1/4)
Ø12.7(1/2)
25.4(1)
21(46.3)
34 / 33 / 32
1, 220-240, 50
1, 220, 60
EEV
CVV-SB 1.0~1.5 x 2C
CVV-SB 1.0~1.5 x 2C
Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m
l/s = CMM x 1000/60
3.6
3,100
12,300
4.0
3,400
13,600
2 x 11 x 21
0.16
Sirocco Fan
19 x 1, 5 x 1
0.76
10.0 / 8.0 / 6.5
353 / 283 / 229
2(20)
10.0 / 8.0 / 6.5
353 / 283 / 229
0(0)
Direct
BLDC
-
Ø6.35(1/4)
Ø12.7(1/2)
25.4(1)
21(46.3)
35 / 34 / 33
1, 220-240, 50
1, 220, 60
EEV
3
/min x 35.3