Indoor unit
2. Specification
Type
Model
Cooling Capacity
Heating Capacity
Casing
Dimensions(WxHxD) Body
Rows x Columns x FPI
Coil
Face Area
Type
Motor Output x Number
Running Current
Fan
Air Flow Rate(H / M / L)
Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Safety Device
Liquid Side
Pipe Connections Gas Side
Drain Pipe(Internal Dia.)
Net Weight
Noise Level(Sound Press, 1.5m, H / M / L)
Power Supply
Refrigerant Control
Transmission cable
Notes:
1. Capacities are based on the following conditions:
Cooling
• Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
Heating
• Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. Wiring cable size must comply with the applicable local and national codes. And "Electric characteristics" chapter should be
considered for electrical work and design. Especially the power cable and circuit breaker should be selected in accordance
with that.
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.
Unit
ARNU07GCEU4
kW
2.2
kcal/h
1,900
Btu/h
7,500
kW
2.5
kcal/h
2,200
Btu/h
8,500
Galvanized
Steel Plate
mm
978 x 639 x 190
inch
38-1/2 x 25-5/32 x 7-15/32
2 x 12 x 19
m
2
0.16
Sirocco Fan
W
19 x 1, 5 x 1
A
0.76
CMM
8.5 / 7.5 / 6.5
cfm
300 / 265 / 229
Direct
BLDC
Microprocessor,
Thermostat for
cooling and heating
Foamed polystrene
Resin Net(washable)
Fuse
mm(inch)
Ø6.35(1/4)
mm(inch)
Ø12.7(1/2)
mm(inch)
12(15/32)
kg(lbs)
20(44.1)
dB(A)
35 / 33 / 31
1, 220-240, 50
Ø, V, Hz
1, 220, 60
EEV
mm
2
CVV-SB 1.0~1.5 x 2C
Floor Standing
ARNU09GCEU4
ARNU12GCEU4
2.8
2,400
9,600
3.2
2,800
10,900
Galvanized
Steel Plate
978 x 639 x 190
978 x 639 x 190
38-1/2 x 25-5/32 x 7-15/32
38-1/2 x 25-5/32 x 7-15/32
2 x 12 x 19
0.16
Sirocco Fan
19 x 1, 5 x 1
0.76
9.5 / 8.5 / 7.5
10.5 / 9.5 / 8.5
335 / 300 / 265
371 / 335 / 300
Direct
BLDC
Microprocessor,
Microprocessor,
Thermostat for
Thermostat for
cooling and heating
cooling and heating
Foamed polystrene
Foamed polystrene
Resin Net(washable)
Resin Net(washable)
Fuse
Ø6.35(1/4)
Ø12.7(1/2)
12(15/32)
20(44.1)
36 / 34 / 32
1, 220-240, 50
1, 220-240, 50
1, 220, 60
EEV
CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C
Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m
l/s = CMM x 1000/60
Floor Standing
3.6
3,100
12,300
4.0
3,400
13,600
Galvanized
Steel Plate
2 x 12 x 19
0.16
Sirocco Fan
19 x 1, 5 x 1
0.76
Direct
BLDC
Fuse
Ø6.35(1/4)
Ø12.7(1/2)
12(15/32)
20(44.1)
37 / 35 / 33
1, 220, 60
EEV
3
/min x 35.3
_ 3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multi v arnu09gtua4Multi v arnu12gtua4Multi v arnu18gtta4Multi v arnu24gtta4Multi v arnu09gtla4Multi v arnu12gtla4 ... Show all