7. External Static Pressure (E.S.P) & Air Flow
ARNU42GM2A4
Setting value
5(49)
90
22.2
95
25.1
100
28.0
105
30.9
110
33.8
115
36.7
120
39.7
125
42.6
130
-
135
-
140
-
145
-
150
-
155
-
Note: 1. The above table shows the correlation between the air rates and E.S.P.
2. The above table shows the available E.S.P. range.
3. If the E.S.P. of the installed indoor is less than the lowest value(as mention in the table), indoor components
can be failed.
16
14
12
10
8
6
4
22.0
Static Pressure (mmAq(Pa))
6(59)
8(78)
-
-
22.3
-
25.4
-
28.5
23.3
31.6
26.8
34.8
30.3
37.9
33.8
41.0
37.3
44.1
40.8
-
44.3
-
-
-
-
-
-
-
-
Fan Performance
ARNU42GM1A4
95 SV
100 SV
27.0
32.0
10(98)
12(118)
-
-
-
-
-
-
-
-
-
-
24.4
-
28.3
23.5
32.2
27.5
36.1
31.6
40.0
35.6
43.9
39.7
-
43.7
-
-
-
-
120 SV
110 SV
37.0
42.0
Air Flow (CMM)
Ceiling Concealed Duct(Middle Static)
(Unit: CMM)
14(137)
15(147)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
26.1
-
30.4
28.0
34.6
32.4
38.9
36.8
43.1
41.2
-
45.6
150 SV
140 SV
130 SV
47.0
_ 23