LG MULTI V ARNU07GTUA4 Engineering Product Data Book page 204

Hide thumbs Also See for MULTI V ARNU07GTUA4:
Table of Contents

Advertisement

Indoor unit
10. Installation
10.2 Ceiling dimension and hanging
bolt location
n Installation of Unit
Install the unit above the ceiling correctly.
CASE 1
POSITION OF SUSPENSION BOLT
• Apply a joint-canvas between the unit and duct to absorb
unnecessary vibration.
• Apply a filter Accessory at air return hole.
• Refer to the Dimensions.
Dimension
A
B
Chassis
BG
1232 1182
BR
1282 1230
Dimension
A
B
C
Chassis
B8
1622 1565 580 292 695 1400 460 1122 1680 390 445 15
• Install the unit leaning to a drainage hole side as a figure
for easy water drainage.
CASE 2
POSITION OF CONSOLE BOLT
• A place where the unit will be leveled and that can sup-
port the weight of the unit.
• A place where the unit can withstand its vibration.
• A place where service can be easily performed.
NOTE:
• Throughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable amount
of oil steam and flour adhere to the fan, the fin of the heat
exchanger, resulting in heat exchange reduction, spraying, dis-
persing of water drops, etc.
In these cases, take the following actions:
• Make sure that the ventilation fan for smoke-collecting hood on a
cooking table has sufficient capacity so that it draws oily steam
which should not flow into the suction of the air conditioner.
• Make enough distance from a cooking room to install the air
conditioner in such a place where it may not suck in oil steam.
2. Avoid installing air conditioner in such circumstances where cut-
ting oil mist or iron powder is in suspension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is
stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generat-
ed.
5. Avoid places near high frequency generators.
30 _
Ceiling Concealed Duct (High Sensible)
(Unit:mm)
C
D
E
F
(G)
H
355
47
450
30
87
830
477
56
590
30
120
1006
D
E
F
G
H
I
J
BG/BR Chassis
I
186
294
B8 Chassis
K
L
E C
G D
A
B
(G)
H
Drainage hole
A
K
B
J
F
H
I
M10 Nut
X 4
M10 washer
X 4
M10 washer
X 4
M10 Nut
X 8
L

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multi v arnu09gtua4Multi v arnu12gtua4Multi v arnu18gtta4Multi v arnu24gtta4Multi v arnu09gtla4Multi v arnu12gtla4 ... Show all

Table of Contents