Indoor unit
8. Electric Characteristicss
Model
Type
ARNU09GTR*4
ARNU15GTR*4
ARNU09GTR*4
ARNU15GTR*4
Symbols:
MCA : Min, Circuit Amps(A)
MFA : Max. Fuse Amps(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amps(A)
IFM : Indoor Fan Motor
10 _
Compact Model
Units
Hz
Volts
TR
50
220-240
TR
TR
60
220
TR
Power Supply
Voltage Range
MCA
MFA
0.25
15
Max:264
Min:198
0.25
15
0.25
15
Max:242
Min:198
0.25
15
Note :
1. Voltage range
Units are suitable for use on electrical systems where volt-
age supplied to unit terminals is not below or above the listed
range limits,
2. Maximum allowable voltage unbalance between phases is 2%
3. MCA/MFA
MCA=1.25 x FLA
MFA≤ 4 x FLA
(Next lower standard fuse rating. Min. 15A)
4. Select wire size based on the MCA
5. Instead of fuse, use Circuit Breaker.
IFM
Input(W)
kW
FLA
Cooling Heating
0.043
0.2
30
0.043
0.2
30
0.043
0.2
30
0.043
0.2
30
30
30
30