Huawei FusionModule1000A40 Installation Manual page 45

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One
Data Center
Installation Guide
Item
Model/Function
Power cable
● Electronic|Electric Cable, 600 V/1000 V, ZA-YJV, (4 x 120
+ 1 x 70) mm
Blue, Black), 322 A, CE
● Connects mains input power cables.
Insulation
Insulates cables onsite.
tape
Terminal
● Bare crimping terminal, DT, 120 mm
plating
● Connects mains input power cables.
● Bare crimping terminal, DT, 70 mm
plating
● Connects mains input power cables.
Ground cable
● Bare crimping terminal, DT, 95 mm
terminal
● Electronic|Electric Cable, 450 V/750 V, 60227 IEC 02
(RV), 95 mm
Bolt for
M12x30 stainless steel bolt assembly
securing the
ground
copper bar
Heat shrink
● Diameter: 50 mm; radial shrinkage: 50%; operating
tubing
temperature range: 55°C to 105°C
● Connects mains input power cables.
SIM card
The SIM card is installed in a card slot in the ECC800-Pro
main control module. The SIM card must support GSM
and WCDMA.
MicroSD card
The microSD card is installed in a card slot in the ECC800-
Pro main control module. The capacity ranges from 16 GB
to 128 GB. The recommended capacity is 32 GB.
Issue 07 (2022-12-15)
2
, Black (4+1 Cores: Yellow, Green, Red,
2
,Yellow/Green, 258 A, CCC, CE
NO TE
● This table may not list some tools required at specific sites. Onsite installation personnel
and technical support personnel should prepare tools based on site requirements.
● Some dedicated tools and installation materials provided with the equipment may not
be listed in this table.
● Preventive measures should be applied before installation to avoid water seepage into
pre-fab. modules and equipment in the case of a sudden change in the weather.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation Preparations
2
, M12, 380 A, tin
2
, M12, 260 A, tin
2
, M12, tin plating
Quantity
Depending on site
requirements
1 roll
18 PCS
5 PCS
Configure 1 PCS for
each ground point.
Configure 1 PCS for
each ground point.
Colors subject to
local regulations, 10
m long for each
1 PCS
1 PCS
37