Huawei FusionModule1000A40 Installation Manual page 71

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One
Data Center
Installation Guide
Figure 6-7 Assembling a step ladder
Step 2 Place the step ladder in the middle 5–10 mm away from the outward opening
door of the pre-fab. module, and mark mounting holes on the concrete pad for
the step ladder.
Step 3 Drill mounting holes using a hammer drill.
● When you drill a hole using a hammer drill, keep the drill bit perpendicular to the ground
and hold the drill stock firmly with both hands to prevent irregular drilling and damage to
the ground.
● If the ground is too hard and smooth for the drill bit to fix its position, use a chisel to punch
a pit before drilling.
Step 4 Rotate nuts onto expansion sleeves to prevent the expansion sleeves from
fluttering.
Step 5 Knock the expansion bolts vertically into mounting holes until the flat washers are
flush with the floor.
Step 6 Remove the nuts, spring washers, and flat washers.
Figure 6-8 Installing an expansion bolt (unit: mm)
(A) M12 bolt
Issue 07 (2022-12-15)
NO TE
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Installing External Accessories for Pre-fab. Modules
(B) Spring washer
(C) Flat washer
63