Huawei FusionModule1000A40 Installation Manual page 87

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One
Data Center
Installation Guide
Procedure
Step 1 Wrap the electric heating belt around the drainpipe and water refill pipe outside
the pre-fab. module.
Figure 9-4 Wrap the electric heating belt around the drainpipe and water refill
pipe
Step 2 Secure the temperature probe to the pipe using a cable tie.
Figure 9-5 Secure the temperature probe
Step 3 Connect the electric heating belt and temperature probe to the controller.
Issue 07 (2022-12-15)
NO TE
Secure the temperature probe to the position on the water refill and drainage pipe. The
position is the point where the electric heating belt is wrapped 50 cm long around the
water refill and drainage pipe from the water refill and drainage pipe port.
Copyright © Huawei Digital Power Technologies Co., Ltd.
9 Installing Devices Inside Pre-fab. Modules
79

Advertisement

Table of Contents
loading

Table of Contents