Procedure
Step 1 Move the fire extinguisher cylinder using a pallet truck to a position near the
container door closest to the installation position.
Do not move the fire extinguisher cylinder over a long distance by hands.
Step 2 Move the fire extinguisher cylinder to the installation position and secure it using
steel straps.
Keep the pressure gauge panel outwards so that people can view the reading,
which also facilitates later maintenance.
Step 3 Connect the hose to the pneumatic switch.
1.
Step 4 Connect the fire extinguisher cylinder to the fire extinguishing pipeline.
Issue 07 (2022-12-15)
NO TICE
NO TICE
NO TE
Wrap the threads with sealing tape to ensure air tightness.
Connect one end of the pneumatic switch hose to the pneumatic switch and
the other end to the container valve of the fire extinguisher cylinder.
Figure 9-16 Connecting the pneumatic switch hose to the container valve
Copyright © Huawei Digital Power Technologies Co., Ltd.
9 Installing Devices Inside Pre-fab. Modules