Siemens SICHARGE UC Installation And Commissioning Manual page 34

Hide thumbs Also See for SICHARGE UC:
Table of Contents

Advertisement

Connecting cable L1, N
No.
1
Remove the sheath of the power supply cable to a length of approx. 5 cm
2
Select a wire end ferrule for the appropriate conductor cross-section
3
Strip the insulation from the end of the conductor so that the remaining insulation extends up to
the ferrule
4
Properly attach the wire end ferrule to the conductor end
5
Insert the wire end ferrule into the terminal strip of the respective conductor
6
Check the connection of the conductor to the terminal
Attaching the power supply cable
No.
1
Secure the power supply cable after the connection to the cable duct
Connecting the DC cable
Connecting the PE conductor
No.
1
Remove the sheath of the cable to connect the cable lug
2
Choose a cable lug for the appropriate conductor cross-section
3
Strip the insulation from the end of the conductor so that the remaining insulation extends up to
the cable lug
4
Fasten the cable lug correctly to the end of the conductor
5
Insert the cable lug into the grounding connection
6
Tighten the nut at the grounding connection with a tightening torque of 45 Nm
7
Check the connection between the PE conductor and the grounding connection
8
Apply sealing paint
9
Document the characteristics of the cable used for the installation
Type of cable
Cable cross section
Cable length
Connecting cable L1, N
No.
1
Remove the sheath of the cable to connect the cable lug
2
Choose a cable lug for the appropriate conductor cross-section
3
Strip the insulation from the end of the conductor so that the remaining insulation extends up to
the cable lug
4
Fasten the cable lug correctly to the end of the conductor
5
Insert a shrink-on sleeve over the cable lug. The shrink-on sleeve must extend slightly beyond the
insulation of the cable and cover the crimping point of the cable lug
6
Use a suitable tool to heat the shrink-on sleeve
Installation and Commissioning Checklist for SICHARGE UC
Product Information, 03/2023, A5E52548271-AA
Checklist item
Checklist item
Checklist item
Checklist item
SICHARGE UC Dispenser
4.3 Connection
P
F
N/A
P
F
N/A
P
F
N/A
P
F
N/A
33