SICHARGE UC Dispenser
4.3 Connection
Connecting cable L1, N
No.
7
Plug the DC+ cable lug onto the DC+ busbar
8
Tighten the screw with the DC+ cable lug with a tightening torque of 45 Nm
9
Insert the DC- cable lug onto the DC- busbar
10
Tighten the screw with the DC cable lug with a tightening torque of 45 Nm
11
Verify that the DC conductor is connected to the DC terminals
12
Apply sealing paint
Connecting the ethernet cable
Connecting the ethernet cable
No.
1
Insert the Ethernet cable into the SICHARGE UC Dispenser
2
Route the cable to the shield terminal
3
Hold the Ethernet cable on a clamp of the shield terminal
4
Record the position of the clamp on the sheath of the cable
5
Expose the braided shield of the marked area around the entire cable
6
Push the cable, at the exposed point, into the clamp of the shield terminal
7
Check the contact between the clamp and the cable shield
8
Route the cable further to the Ethernet switch
9
Insert the RJ45 plug of the Ethernet cable into a free connection of the SICHRAGE UC Dispenser
Ethernet switch -KF22
10
Document the characteristics of the cable used for the installation
Type of cable
Cable length
Fastening the cable
No.
1
Secure the Ethernet cable after the connection to the cable duct
Note
Lay Ethernet cable + power cables parallel and with at least 20cm distance to each other. Low
voltage + high voltage only to cross at 90° angle
34
Checklist item
Checklist item
Checklist item
Installation and Commissioning Checklist for SICHARGE UC
Product Information, 03/2023, A5E52548271-AA
P
F
N/A
P
F
N/A
P
F
N/A