4.2

Installation

Installing the dispenser on the floor
No.
1
Connect the transport lugs of the SICHARGE UC Dispenser and the lifting equipment
2
Lift the SICHARGE UC Dispenser vertically from the transport pallet
3
Transport the SICHARGE UC Dispenser suspended to the location
4
Position the SICHARGE UC Dispenser on the mounting surface using the bolt anchors
5
Guide any underground cables into the mounting base of the SICHARGE UC Dispenser
6
Check whether the alignment of the SICHARGE UC Dispenser with the bolt anchors of the mount-
ing surface is correct
7
Lower the SICHARGE UC Dispenser onto the base area
8
Place the washers on the bolt anchors
9
Attach a bolt lock to the bolt anchors. We recommend LOCTITE 243
10
Screw the cap nuts onto the bolt anchors
11
Tighten the nuts with the tightening torque of the bolt anchors as per the manufacturer's instruc-
tions
12
Seal the openings from the mounting surface to the mounting plate with a suitable sealant to
prevent the ingress of moisture, animals and insects
13
Remove the two transport plates on the rear of the SICHARGE UC Dispenser. Keep the transport
plates
Installing the dispenser to the wall/ceiling
No.
1
Mount the shackle into the holes on the right and left of the mounting rail
2
Attach the shackles to the lifting equipment. Only use suitable and approved lifting equipment
3
Lift the SICHARGE UC Dispenser vertically from the transport pallet
4
Transport the SICHARGE UC Dispenser suspended to the location
5
Position the SICHARGE UC Dispenser on the mounting surface using the bottom bolt anchor
6
Check whether the alignment of the SICHARGE UC Dispenser above the bottom bolt anchor of the
mounting surface is correct
7
Lower the SICHARGE UC Dispenser onto the bottom bolt anchor
8
Attach the washers to the bottom bolt anchors
9
Screw the cap nuts onto the bottom bolt anchors
10
Remove the lifting gear and the shackles from the top mounting rail
11
Slide the SICHARGE UC Dispenser onto the top bolt anchor up to the mounting surface
12
Attach the washers to the top bolt anchors
13
Attach a bolt lock to the top bolt anchors. We recommend LOCTITE 243
14
Screw the cap nuts onto the top bolt anchors
15
Unscrew the bottom cap nuts a little bit
16
Attach a bolt lock to the bottom bolt anchors. We recommend LOCTITE 243
17
Tighten all nuts with the tightening torque of the bolt anchors as per the manufacturer instruc-
tions
Installation and Commissioning Checklist for SICHARGE UC
Product Information, 03/2023, A5E52548271-AA
Checklist item
Checklist item
SICHARGE UC Dispenser
4.2 Installation
P
F
N/A
P
F
N/A
29