FusionCol8000-C210 In-room Chilled Water Smart
Cooling Product
User Manual (2022, Netherland GS)
Figure 5-8 Setting SNMP communications parameters
Step 2 Set SNMP Version based on site requirements, and then tap Submit.
●
●
Step 3 Set Read Community and Write Community.
1.
2.
Step 4 Add a SNMPv3 user.
1.
2.
Issue 01 (2022-12-30)
When SNMP Version is set to ALL or SNMPv1&v2c, you can set Read
Community and Write Community.
When SNMP Version is set to ALL or SNMPv3, you can add an SNMPv3 user.
CA UTION
SNMPv1&SNMPv2c are insecure protocols. SNMPv3 is recommended.
Tap the text box next to Read Community, set the read community
parameter based on the actual plan, and tap Submit.
Tap the text box next to Write Community, set the write community
parameter based on the actual plan, and tap Submit.
Tap Add under SNMP V3.
Set User Name, Auth Protocol, and Prop Protocol based on the actual plan.
MD5 and DES protocols are not secure. It is recommended that you set Auth
Protocol to SHA2-512, and set Prop Protocol to AES-256. The following
operations use the recommended settings as an example.
Figure 5-9 Setting the protocol type
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Power-On Commissioning
98