Table 4-5 Component checklist
Check Item
Equipment
Water pan
Fan
Air filter
Differential
pressure
switch
Chilled water
valve
Exhaust valve
Drainage
valve
Pipe
connection
Issue 01 (2022-12-30)
Expected Result
The equipment is installed properly
without any tilt.
The equipment is secured to the bottom
support using bolts.
The foreign matter inside the equipment
such as cable ties and sundries has been
cleaned up.
The anchor baffle plates have been
installed.
The sundries in the water pan have been
removed.
There are no sundries inside the fan.
The air filter is correctly installed
according to the airflow direction marked
on the frame.
The cable ties are securely tightened
around the pressure inlet tube.
The pressure inlet tube is not blocked or
bent.
The chilled water valve and its actuator
are securely installed.
The chilled water connector joints have
been tightly wrapped with thermal
insulation foam, and no metal or hose is
exposed.
Cables are securely connected to the
chilled water valve and its actuator. The
manual button on the actuator is reset
(ejected state).
The exhaust valve is closed.
The drainage valve is closed.
Water has been filled and air has been
exhausted.
The hose clamp and cable ties of the
condensate pipes are secured.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 System Installation
Check Result
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed